ASTM C78

Created by Juan Ortiz

ASTM is or isnt comparable to single point loading
Is not; lower strengths

1/32

TermDefinition
ASTM is or isnt comparable to single point loading
Is not; lower strengths
Modulus of Rupture
R; ultimate strength
Sawing and specimen prep will affect results
True
Smaller specimens will have higher or lower strengths
Higher
Span length
Distance between bottom rollers; three times depth
Support blocks height
2.5 inch (65mm)
Support block planeness
0.002 inch
Supports should arc at least how many degrees
45 degrees (0.8 rads)
Span length shall not vary by more than ____
0.05 inch
Bigger aggregates
Bigger beams; lower strength
Surface drying
Reduces strength; microcracks from
Which face propagates
Tension side (bottom)
The point of max load
Form crack from tensile side
Finished face should face which way during testing
To the side
Apply intial load to ___ % of expected max load
3-6%
Use a large ___ in feeler gauge
0.015 in Grind or cap if it passes through
Use a small ___ in feeler gauge
0.004 in Use leather strips if it passes through Test as is if it doesnt pass through
Leather shims dimensions
0.25 in thick 1in - 2 inch wide cover entire specimen Use on all 4 locations
Capping beams
if 0.015 in feeler gauge passes though Cover entire face Include on depth calulations Gysum or neat cement
Load rate per min
125 - 175 psi/min 0.9 - 1.2 MPa/min
Load Rate per sec
2-3 psi/min 0.015-0.02 MPa/min
How to calculate "a"
Take average of three measurements from support line to crack
Which side is used to calulate "a"
tensile side
a > L/6
In middle third
What percent is acceptable to off middle third
5%
Depth vs Breadth
Depth is top to bottom Breadth is left to right
Calculate b and d
Take average of three measurements after testing: choose smaller end
Formula for crack whichin middle third
PL/(b)(d^2)
Formula for crack which 5% of middle third
3Pa/(b)(d^2)
Report MOR to what psi
5 psi
Report avg breadth and depth to what inch
0.05 inch
T or F During first half test speed can be increased
False