Per the IMC, air intake openings shall be located not less than ____ horizontally from any hazardous or noxious contaminant source, such as vents, streets, alleys, parking lots and loading docks?
10 Feet

1/35

TermDefinition
Per the IMC, air intake openings shall be located not less than ____ horizontally from any hazardous or noxious contaminant source, such as vents, streets, alleys, parking lots and loading docks?10 Feet
Per the UMC, appliances such as suspended-type infrared heaters shall be fixed in position independent of gases and electric supply lines with hangers and brackets that are substantially made of?Noncombustible material
Most commercial refrigerating systems use hot gas mufflers for comfort cooling in air conditioning. Mufflers are usually installed near the condenser, usually vertically. A muffler that is not installed correctly could trap what? Oil
In an R-22 system, evaporator pressure is 60 pounds. What is the corresponding saturated refrigerant temperature?34 Degrees F
What factors must be directly considered in the determining heat loss for a residential structure?Difference between indoor and outdoor temperature
Pressure relief device located within a machinery room shall terminate at what distance from any opening to the building?20 Feet
The approximate heat content of natural gas is2,500 to 3,200 BTU/FT3
When considering a bely drive motor, where the adjustable motor pulley halves are moved closer together, the fan speed shall? Increase
According to the International Mechanical Code, buildings with permanently installed rood access ladders shall maintain a minimum unobstructed clearance at the base of the landing measuring?30"x 30"
Every pressure relief valve on a mechanical refrigeration system shall be connected to the refrigerant discharge pipe of the compressor it serves. Where shall these relief valves be located?Between the compressor and the first shutoff valve at the condenser
Based on ACCA's Manual D, which of the following is designed values or core input is required to begin duct sizing calculations?Blower CFM
Which of the following is not a factor in heat loads for a structure?Heat produced by the outside walls
Which of the following refrigerant will have the MOST static loss of pressure across a liquid line with a a 30-foot vertical line?R-134A
What establishes the low side pressure in the evaporator?Refrigerant control
The rupture disc setting for low pressure chillers is normally set at 15 PSIG
Every passageway serving equipment located in an attic or furred space shall have solid, continuous flooring from the access opening to the required working space. The platform shall extend In the front of the equipment
The latent heat of vaporization of R-410A117 BTU/LB
Commerical kitchen grease ducts shall be designed for the type of cooking appliance and hood served. If the installation calls for a Type I hood, the grease duct must be a minimum thickness steel gage of ____.16 Gage
A machinery room contains mechanical refrigerating equipment with a ventilating exhaust discharge. What must be the MINIMUM distance between the machinery room's exhaust discharge and any exterior door or window? 20 Feet
Which type of ice maker is used to make ice flakes?Auger
Per the textbook MR & AC, in the operation of a hot gas defrost system, the compressor runs, the hot-gas solenoid valve opens, and the ____ fans stop turning. The hot compressed vapor rushes through the hot-gas defrost valve and into the _____, melting accumulated frost, the refrigerant then returns to the compressor through the suction line?Evaporator
A run capacitor's primary function is to provide a phase shift to the motor windings, thereby optimizing motor performance. A slightly larger capacitor can sometimes improve motor efficiency, but going much larger can lead to other problems. So, when replacing a motor run capacitor, the capacitance can be increased up to _____ of the original valve?10%
What would be the capacity in cubic feet of gas per hour. Example: The 1/2 gas pipe installation will use Schedule 40 metallic pipe, natural gas, less than 2 PSI inlet pressure, 0.5 inch W.C pressure drop, 0.60 specific gravity? Assume that the length of pipe will be 50 feet 72
If an employee earns $1,347 each week, what would be the tax liability for the employer and employee for both Social Security and Medicare?$206
When calculating the percentage of compression of a flexible duct, the change in length divided by the original length calculates the compression percentage. So, a 10-foot flex duct is between two connectors that are 7-feet apart is what percentage compressed?30%
According to the Uniform Mechanical Code, what is the minimum clear head room required below equipment situated over a passageway in a refrigeration machinery room?7.25 Feet
An appliance is located in a confined space with all air taken from the outside by means of two vertical ducts. Each opening for combustion shall be a minimum of one square inch per 4,000 BTU/H
All of the following is required and included in the maintenance of air conditioning and refrigeration, exceptinstallation or replacement of complete systems
When must an approved smoke detector be installed in an air movement system?When a return air duct has a design capacity of over 2000 CFM
What is the component that releases heat from mechanical refrigeration system?Condenser
What diameter steel duct will deliver 400 CFM at 900 FPM9 inch
A direct vented appliance rated at 50,000 BTU/H shall be located so that a minimum clearance of ____ is maintained between vent terminals and from any opening through which combustion products enter the bulding9 inches
What effect does a thermostatic expansion valve with a discharge power element have on an evaporator?Starved Evaporator
What is the static pressure for a 12-inch flex duct with a 15% compression delivering 900 CFM?0.50
Per the MR&AC, an air filter made of ____ can remove solid particles, odor causing gases and bacteria.Activated Carbon